Temperature controller fault 1: The device does not display after being powered on.
Solution: First, check if the device's segment is already connected to the zero live wire, and ensure that the zero live wire power supply can operate normally.
Next, check if there is any looseness in the wiring between the LCD motherboard and the device driver power supply, and relevant tightening measures need to be taken. Pay attention to whether the switch of the temperature controller has been turned on and meets the specified standards.
When wiring the temperature controller, it is necessary to check the relevant voltage, current, and other issues of the wiring power supply in advance.
Q
Press the "Manual/Automatic" button on the panel, and the fan indicator light will light up. Why does the fan not start?
1. The fuse on the rear panel of the temperature controller should be checked for integrity.
2. Check whether the wiring terminal of the temperature controller fan is active or passive (active: refers to the fan wiring terminal that can output a voltage of 220VAC/10A when starting the fan, and the fan can be directly connected to the wiring terminal; passive: refers to the fan wiring terminal that is equivalent to a switch, and the fan must be connected to an external power source to start the fan).
3. Check if the fan is faulty (it can be determined by checking the DC resistance of each fan with a multimeter).
Q
Why does the temperature controller not display after power on?
1) Check if the power supply of the temperature controller is properly connected.
2) Check if the power switch of the temperature controller is turned on (only embedded and BWD3K series temperature controllers have a power switch).
3) Check if the power supply voltage of the temperature controller is within the allowable voltage range (220VAC ± 20%=175-265VAC).
Q
How to determine whether the temperature controller is working properly on site?
On site, connect the power cord, sensing cord, and fan cord to the temperature controller, and observe when powered on: if the three-phase temperature display is basically balanced, there is no fault alarm, and the overtemperature alarm indicator light and trip indicator light go out, press the "Manual/Automatic" button on the panel by hand. If the fan indicator light is on, the fan should start and then press the "Manual/Automatic" button. The fan indicator light will light up and go out, and the fan should stop rotating at this time, It can be basically judged that the temperature controller is working normally.